Transcript
2. Find the equivalent lengths of all fittings and flexible tube sections by using Table 8. TABLE 8. EQUIVALENT LENGTHS OF PIPE FITTINGS (FEET) TYPE OF FITTING NOMINAL DIAMETER (INCHES) 2 2.5 3 3.5 4 5 6 8 10 12 STANDARD ELBOW 5.3 6.4 8.1 9.6 11 14 16 21 26 32 MEDIUM RADIUS ELBOW 4.6 5.4 6.8 8 9 12 14 18 22 26 LONG RADIUS ELBOW 3.5 4.2 5.2 6 7 9 11 14 17 20 45° ELBOW 1.5 2 2.3 2.6 3 4 4.5 6 8 9 STANDARD TEE 13 14 17 19 22 27 34 44 56 67 18 INCH FLEXIBLE TUBE 3 3 3 3 3 3 3 3 3 3 24 INCH FLEXIBLE TUBE 4 4 4 4 4 4 4 4 4 4 3. Find the backpressure at the given exhaust flow per unit length of pipe for each nominal pipe diameter used in the system. In this example, 5 inch and 6 inch nominal pipe is used. Following the dashed lines in Figure 23, 5 inch pipe causes a backpressure of approximately 0.35 inches WC (Water Column) and 6 inch pipe approximately 0.145 inches WC. 4. Add the back pressures for all elements of the example, as follows: Muffler ………………………………………………………………………………………………21.5 One 5 Inch Flexible Tube—O.35 x 4 ft……………………………………………………………….1.4 20 Feet of 6-Inch Pipe—0.145 x 20 ft………………………………………………………………...2.9 One 6-Inch, Long Radius Elbow—0.145 x 11 ft……………………………………………………...1.6 TOTAL EXHAUST BACK PRESSURE (Inches WC)…………………………………………...27.4 5. The calculation indicates that the piping layout is adequate in terms of exhaust backpressure since the sum of the backpressures is less than the maximum allowable backpressure of 41 Inches WC. 23