Discrete 2-, 3-, 4-state Device (P_D4SD)
Execution
The following table explains the handling of instruction execution conditions.
Condition
Description
EnableIn False (false rung)
Handled the same as if the device were Disabled by
Command. The device outputs are de-energized and the
device is shown as Disabled on the HMI. The mode is
shown as ‘NO MODE’. All alarms are cleared.
Powerup (prescan, first scan)
On Prescan, any Commands received before First Scan are
discarded. The device is de-energized. On first scan, the
device is treated as if it were returning from Hand mode:
the instruction state is set based on the position feedback
received from the device.
Embedded P_Mode and P_Alarm instructions are
handled in accordance with their standard powerup
procedures. Refer to the P_Mode and P-Alarm reference
manuals for details.
Postscan
No SFC Postscan logic is provided.
Refer to the Logix5000 Controllers Add-On Instructions Programming Manual,
publication 1756-PM010, for more information.
Rockwell Automation Publication SYSLIB-RM028C-EN-P - August 2014