Download Series 625 handbook
Transcript
625ManualIss1.doc 2.8.3. It is recommended that a 120 Ohm resistor be connected across the RX terminals of the last unit on the loop, once again to prevent reflections. 2.8.4. Please remember that when the unit is the first in the loop, it will be connected to a ‘master’ unit. This would normally be a computer with an RS485 port. 2.8.5. In this case, the TX and RX terminals of the master should be connected to the RX and TX terminals respectively of the Series 625 unit. Please observe polarity. 2.8.6. To change the communications configuration to 2-wire RS485, remove the left hand side cassette, flip up the lid and remove the processor (lower) board. Move JP6 from position ‘B’ to position ‘A’. Replace the board, close the lid and replace the cassette 3. Connecting the inputs and outputs When the units are connected terminals may be live and the removal of parts is likely to expose live parts. The unit must be disconnected from all voltage sources (including any potentially hazardous I/O leads) before it is opened for any replacement, maintenance or repair. Any adjustment, maintenance or repair of the opened unit whilst powered must be avoided. It should be carried out only by skilled personnel who are aware of the hazard involved. 3.1. Digital inputs (Low level 10 – 30V). These are current driven and require about 2mA. They are designed to operate from external supplies. Although + and - are specified, either AC or DC inputs may be used. Do not apply voltages in excess of the specified input range. Page 6 of 15 07/01/2008