Chapter 5 PC Link Communication
5.4.7
WRD
Reads D registers and I relays on a word-by-word basis.
● Function
Reads a sequence of contiguous register information on a word-by-word
basis by the specified number of words, starting at the specified register
number.
• The number of words to be read at a time is 1 to 64.
• For the format of response in the event of failure, see subsection
5.1.2.
• The command shown below includes the checksum function. When
performing communication without the checksum, do not include the 2byte checksum element in the command.
● Command/Response (for normal operation)
Number of
Bytes
Command
element
Number of
Bytes
Response
element
1
2
2
1
3
5
1
2
2
1
1
STX
Address
(Station
number)
CPU
number
01
0
WRD
Register
number
Comma
or
space
Number
of words
(n)
Check
sum
ETX
CR
1
2
2
2
4
4
4
2
1
1
STX
Address
(Station
number)
CPU
number
01
OK
dddd1
dddd2
ddddn
Check
sum
ETX
CR
The response is returned in a 4-digit character string (0000 to FFFF) in a hexadecimal pattern.
ddddn: Read data of the specified number of words
ddddn = character string in a hexadecimal pattern
n = 1 to 64
● Example: Reading the Integrated power (uint32; lower-order 2
bytes) (D0001) and the Integrated power (uint32; higherorder 2 bytes) (D0002) of the CW120/121 with address
number 01.
[Command] [STX]01010WRDD0001, 02[ETX][CR]
The Integrated power (uint32; lower-order 2 bytes) (D0001) value
(03E8(HEX)) and the Integrated power (uint32; higher-order 2 bytes)
(D0002) value (00C8 (HEX)) is returned in response to the command
above.
[Response] [STX]0101OK03E800C8[ETX][CR]