Download FINEST 135
Transcript
6.3 Motors You can measure starting (inrush) current, running current, and current imbalance. Inrush current is typically 6 times the value of running current, depending on the motor type. 1. Press the ON OFF pushbutton to turn on this Meter. 7. Turn on the motor. When the motor gets to the desired speed, note the blinking upper bar on the bar graph (inrush rms current), and the displayed level (running rms current). 8. To view the maximum inrush current, press the MIN MAX pushbutton once. 2. Clamp around a motor phase conductor. Be sure the clamp jaws are securely closed, or measurements will not be accurate. 9. Repeat step 6, if necessary. 3. While watching the bar graph, turn on the motor and observe the level of inrush current. In this case, the bar graph is better than the digital display because the bar graph response is faster than the digital display. 6.4 Distribution Transformers 10. To clear RECORD, press the MIN MAX pushbutton for 2 seconds. You can measure excessive current, load balance between phases, true-rms and frequency of neutral current. Truerms measurement yields the effective value. 1. Press the ON OFF pushbutton to turn on this Meter. 2. Clamp around a phase wire of the transformer. Be sure the clamp jaws are securely closed, of measurements will not be accurate. 3. Observe the display for true-rms current flow. 4. Repeat your measurement for each phase to observe balance. Unbalanced phases cause large neutral currents flow. 5. Clamp around the neutral wire. 4. When the motor reaches the desired speed, observe the running current. 5. Repeat your measurement for each motor phases. Unbalanced current may be caused by a voltage imbalance, or a shorted motor winding. 6. Repeat steps 1 thru 3, then press the MIN MAX pushbutton to enable RECORD. 24 6. Observe the display for true-rms current flow. Any significant flow, with balanced phases, indicates the presence of harmonic currents. 7. Press the Hz pushbutton to measure the frequency of neutral wire. Reading indicates the frequency of the dominant current flow (in case of harmonic current flow, 180Hz reading in a 60Hz system). 8. To freeze the digital display, press the HOLD pushbutton. 9. To measure peak amperes, press the 1mS PEAK pushbutton (PEAK displayed). 25