6.3 Motors
You can measure starting (inrush) current, running current,
and current imbalance. Inrush current is typically 6 times
the value of running current, depending on the motor type.
1. Press the ON OFF pushbutton to turn on this Meter.
7. Turn on the motor. When the motor gets to the desired
speed, note the blinking upper bar on the bar graph
(inrush rms current), and the displayed level (running
rms current).
8. To view the maximum inrush current, press the MIN
MAX pushbutton once.
2. Clamp around a motor phase conductor. Be sure the
clamp jaws are securely closed, or measurements will
not be accurate.
9. Repeat step 6, if necessary.
3. While watching the bar graph, turn on the motor and
observe the level of inrush current. In this case, the bar
graph is better than the digital display because the bar
graph response is faster than the digital display.
6.4 Distribution Transformers
10. To clear RECORD, press the MIN MAX pushbutton for
2 seconds.
You can measure excessive current, load balance between
phases, true-rms and frequency of neutral current. Truerms measurement yields the effective value.
1. Press the ON OFF pushbutton to turn on this Meter.
2. Clamp around a phase wire of the transformer. Be sure
the clamp jaws are securely closed, of measurements
will not be accurate.
3. Observe the display for true-rms current flow.
4. Repeat your measurement for each phase to observe
balance. Unbalanced phases cause large neutral
currents flow.
5. Clamp around the neutral wire.
4. When the motor reaches the desired speed, observe
the running current.
5. Repeat your measurement for each motor phases.
Unbalanced current may be caused by a voltage
imbalance, or a shorted motor winding.
6. Repeat steps 1 thru 3, then press the MIN MAX
pushbutton to enable RECORD.
24
6. Observe the display for true-rms current flow. Any
significant flow, with balanced phases, indicates the
presence of harmonic currents.
7. Press the Hz pushbutton to measure the frequency of
neutral wire. Reading indicates the frequency of the
dominant current flow (in case of harmonic current
flow, 180Hz reading in a 60Hz system).
8. To freeze the digital display, press the HOLD
pushbutton.
9. To measure peak amperes, press the 1mS PEAK
pushbutton (PEAK displayed).
25