Download PowerFlex 40 Adjustable Frequency AC Drive ! ! ! ! !
Transcript
English-3 Typical Grounding R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 SHLD Disconnecting MOVs To prevent drive damage, the MOVs connected to ground shall be disconnected if the drive is installed on an ungrounded distribution system where the line-to-ground voltages on any phase could exceed 125% of the nominal line-to-line voltage. To disconnect these devices, remove the jumper shown in the figures below. 1. Turn the screw counterclockwise to loosen. 2. Pull the jumper completely out of the drive chassis. 3. Tighten the screw to keep it in place. Jumper Location IP20, NEMA/UL Type Open IP66, NEMA/UL Type 4X Important: Tighten screw after jumper removal. Phase to Ground MOV Removal R/L1 Three-Phase AC Input S/L2 T/L3 Jumper 1 2 3 4