Communication cable should be a twisted pair, 100 - 250 Ohm characteristic impedance (Cat. 5 is ok). The cable should also provide wires for a common reference and shield. Never use a end-of line resistor in the network. The communication cable should not be connected in a loop, it should always be end to end. Each module has been factory set with correct node addresses and labeled accordingly. Do not make any changes. Connections, communication cable RJ-45 1 2 3 4 5 6 7 8 RJ-45 A Ref Ref B Cable RS-485 Shield Signal: Pin: 3 A B 6 4 Ref 5 Ref Shield TIA 568-A: White/Orange Orange Blue White/Blue Section 7.04 A Ref Ref B TIA 568-B: White/Green Green Blue White/Blue 1 2 3 4 5 6 7 8 Use twisted pair cable with screen. Characteristic impedance: 100-250ohm Pin 1,2,7,8: Not connected Main power supplies The Master CPU has terminals for incoming 24VDC power. Up to four power supplies may be connected, which inside the module are wired in parallel by means of high capacity diodes. The resulting common 24VDC power is then made available as a power source to all other modules that are a part of the system. Each of the up to four power supplies are monitored by the Master CPU. Section 7.05 Termination of system The system must be terminated correctly to ensure that all nodes are powered and that they communicate properly. Panel: • The panel should be fixed to the bridge or similar place by means of four screws. • Connect 24VDC power and the communication cable. Output modules: • The output modules should be clamped onto a 35 mm rail using the clip on the rear side of the modules. Copyright © 2005 – 2015 TRANBERG AS. All rights reserved. Page 34 of 40