Download QCPU(Q Mode)/QnACPU Programming Manual (SFC)

Transcript
4 SFC PROGRAM CONFIGURATION
MELSEC-QnA
4.7.6 Operation mode at transition to active step (double step START)
This mode setting designates the operation mode which is to be effective when a follow-up
function such as an operation HOLD step (with transition check) is used to execute a transition to
a step which is already active.
(1) Settings and corresponding operations
A PAUSE, WAIT, or TRANSFER setting can be designated.
The operations resulting from these settings are shown below.
Setting
Operation
Remarks
• A CPU operation error (BLOCK EXE.ERROR) occurs, and • A step range can be
designated for the STOP
CPU operation is stopped.
setting.
• All “Y” outputs switch OFF.
• CPU operation continues, and a WAIT status is established
when the transition condition is satisfied. The WAIT status
• A step range can be
continues until the START destination step is deactivated.
designated for the WAIT
• If a transition WAIT occurs, the previous step is
setting.
deactivated, the output is switched OFF, and the operation
output will not be executed.
• CPU operation continues, the transition occurs, and the
previous step is deactivated and absorbed by the transition
destination step.
PAUSE
WAIT
Active step
TRANSFER (default)
Inactive
Condition satisfied
Active step
Active
Condition satisfied
(2) Transition to HOLD step by double START
The following table shows the transition procedure for transitions to coil HOLD steps, operation
HOLD steps (with transition check), and operation HOLD steps (without transition check)
which occur when the double START condition is satisfied. These transitions occur without
regard to the settings described at item (1) above.
Setting
PAUSE,
WAIT,
TRANSFER
Operation
• The TRANSFER setting applies to all operations, regardless of the
setting.
• At coil HOLD steps
......... The operation output is restarted, and a transition condition
check begins.
The PLS instruction for which the input conditions have
already been established is non-executable until the input
conditions are turned on again.
• At operation HOLD steps (without transition check)
........ A transition condition check begins.
• At operation HOLD steps (with transition check)
........ Operation continues as is.
Active step
Inactive
Remarks
• Following the double
START, execution of all
subsequent steps where
transition conditions are
satisfied will occur according
to the step attributes.
Transition condition satisfied
Coil HOLD step or
operation output step
(without transition check)
Active
Transition condition
is checked
(No transition condition check)
4 - 73
4 - 73