Profibus-DP
Start-up behavior
IM 208 - Master
When the IM 208 interface is connected to a supply (Power On) the
configuration data is read from the memory card, verified and stored into the
internal RAM of the IM 208.
At power on the master will automatically change to RUN mode if the
operating mode selector is set to RUN and if the parameters are acceptable.
In RUN mode the LED’s RN and DE are on. When all the configured slaves
have become available in the data exchange the ER-LED is extinguished.
In STOP mode the outputs of the allocated slaves will be set to 0 if the
parameters are valid. Although no communications will take place, the
master will remain active on the bus using current bus parameters and
occupying the allocated bus address. To release the address the Profibus
plug must be removed from the IM 208 interface.
IM 253 - slave
After power on the Profibus coupler executes a self test. This test checks
the couplers internal functions and the communications via the back panel
bus.
When the bus coupler has been initialized properly its status is set to
“READY”.
When the status is READY the slave receives the parameters that are
located in the master and that were previously configured. When the
parameters have been validated the status of the slave changes to “Data
Exchange” DE.
The DE-LED is turned on when the module is communicating. Should
communication errors occur on the back panel bus the Profibus coupler will
be placed in STOP mode and it will be re-started after app. 2 seconds. The
RD-LED blinks when the test has returned a positive result.