256
Chapter 9: Configuring Events
only on specific computers, specify an event name and use the Citect Computer
Setup Wizard (Custom setup) to specify which CitectSCADA computer(s) will
run the event. The event name does not have to be unique, you can specify many
events with the same name.
Enter a value of 16 characters max.
Time
The time of day to synchronize the Period in hh:mm:ss (hours:minutes:seconds).
If you do not specify a time, Period is synchronized at 00:00:00 (i.e. midnight).
Enter a value of 32 characters maximum.
Period
The period to check for the event, in hh:mm:ss (hours:minutes:seconds). Enter a
value of 32 characters maximum. Alternatively you can specify:
„
A weekly period by entering the day of the week to check for the event, e.g.
Monday, Tuesday, Wednesday, etc.
„
A monthly period by entering the day of the month to check for the event,
e.g. 1st, 2nd, 3rd, 4th, 5th, etc.
„
A yearly period by entering the day and the month to check for the event,
e.g. 1st January, 25th February, and so on. The day and month must be
separated by a space.
If you do not specify a period or time, the period defaults to one second. If you
do not specify a period, but do specify the time, the period defaults to one day.
Trigger
The Cicode expression (or Variable tag) which is used to determine whether the
event Action is executed. This expression is checked every one second. Enter a
value of 64 characters maximum.
Action
The commands to execute. Enter a value of 64 characters maximum.These
commands will execute in the following circumstances:
„
When the specified Time and Period occurs, and the Trigger condition is
TRUE or blank.
„
When the Trigger becomes TRUE, and the Time and Period field are blank.
The Trigger must become FALSE and TRUE again for the action to reexecute.
Comment
Any useful comment. Enter a value of 64 characters maximum.