3.4 Configuration of the arc protection system 3.4.1. 3 VAMP 221 arc protection system operation and troubleshooting VAMP 221 Checking system configuration To check system configuration in INFO mode, do the following: Figure 3.4.1-1 Checking system configuration in INFO mode Select the INFO mode using the up and down arrow keys. You can read the I/O unit address and the number of sensors stored in the memory from the central unit's display. Use the side arrow keys to move between the I/O units. When the correct I/O unit shows on the display, press S to activate the INFO mode. To check the number of connected sensors, press E. The central unit will display the number of sensors connected to the I/O unit for two seconds, after which it will show the number of sensors stored in the memory. If the numbers are not the same, see section 3.1.3. NOTE! Checking system configuration will not affect the configuration stored in the central unit's memory. If you wish to modify the configuration, see section 3.4. 58 V221/EN M/B019