Download VAMP 221 manual- Arc flash protection

Transcript
3.4 Configuration of the arc
protection system
3.4.1.
3 VAMP 221 arc protection system
operation and troubleshooting
VAMP 221
Checking system configuration
To check system configuration in INFO mode, do the following:
Figure 3.4.1-1 Checking system configuration in INFO mode






Select the INFO mode using the up and down arrow keys.
You can read the I/O unit address and the number of
sensors stored in the memory from the central unit's
display.
Use the side arrow keys to move between the I/O units.
When the correct I/O unit shows on the display, press S
to activate the INFO mode.
To check the number of connected sensors, press E.
The central unit will display the number of sensors
connected to the I/O unit for two seconds, after which it
will show the number of sensors stored in the memory. If
the numbers are not the same, see section 3.1.3.
NOTE! Checking system configuration will not affect the configuration
stored in the central unit's memory. If you wish to modify the
configuration, see section 3.4.
58
V221/EN M/B019