The settings of a compliant system should be recorded, as it is possible by changing certain programmable functions to make the system noncompliant. If functions are changed, it is recommended that the system is retested if continuing compliance is in any doubt. Note: For EN 54-20 compliant installations the detector requires that the flow thresholds be set manually to ± 6% of the nominal value, after the FastLearn phase is completed. For example, if the flow rate is 64% after the completion of the FastLearn period, the user must manually set the low flow threshold to 58% and the high flow threshold to 70%. vi LaserSense HSSD-2 Aspirating Smoke Detection System Installers Handbook