22
NOTE: THERE ARE NO USER
SERVICEABLE PARTS.
1. Check the 24V Cable & Connections
visually for condition.
2. Check the unit and its pipework
for any evidence of leaks visually.
TWICE ANNUALLY: By a competent
service \ maintenance engineer
IT IS NOT RECOMMENDED THAT THE
END USER MAKES ANY
ADJUSTMENTS OR CARRIES OUT
ANY MAINTENANCE OTHER THAN :
It is important that all the vents and grills
are kept clear (including condenser grills
where applicable).
Do not use a water or stream hose to
clean the unit whilst still installed.
1. Isolate the unit from the Base Cooler
electricity supply.
2. Open the unit to access both sides
of the condenser matrix and remove
any extraneous debris from the unit
or its casing preferably using a
vacuum cleaner or brush.
3. Check unit for electrical safety.
Do not use a water or steam hose to
clean the unit whilst still installed.
Methods of cleaning
ADJUSTMENTS/MAINTENANCE
REQUIREMENTS
Section 4
Faulty
pump motor
Yes
Check for 240V
supply at
connection
Yes
Is the pump
plugged into its
mating connector
No
No
No
Yes
No
Is the glycol
mixture
recirculating
adequately
Yes
Re-site heat dump
closer to glycol
module.
Yes
Is the heat dump
sited more than
12m lift away from
the glycol module
No
Is the glycol
mixture
recirculating
adequately
Possible air lock in
system. Bleed air
lock out of system
and re-prime
No
Are the glycol
lines connecting
the heat dump
blocked, collapsed
or restricted in any
way.
Yes
Are the shut off
valves open on
the connections to
the pump
Is the glycol level
in the header tank
between Max and
Min marks
Top up to
maximum level
and check for leaks
No
Ensure tubing is the correct type
(Cobracol) and ensure pipes are
not secured together and are
away from heat sources
Internal wiring
fault or faulty
electrical feed
from base unit
Plug pump into
connector
IS THE GLYCOL
PUMP
OPERATING
No
Yes
Yes
No
Yes
Faulty pump
System O.K
Clear blockage or
restriction
Open shut off
valves
System O.K
FAULT DIAGNOSIS FLOW CHART - GLYCOL MODULE (WATER COOLED UNITS)
35
Section 10