normally required. Some solar panels have the charge controller already built in, if that type
of panel is used another controller is not needed.
The components required will vary depending on the location, for example Alaska in
winter has very little daylight available, so a solar system there would need much greater
capacity than one located in Arizona. It is usually possible to connect the RFScada directly to
an existing 12 or 24 Volt solar power system that is being used to power other equipment
such as RTU’s or transducers, simply connect the external source to the DC input.
Cabinet Construction
The brochure states that the RFScada has a corrosion resistant NEMA 4X rated cabinet but
the antenna is located inside. Doesn’t the stainless steel cabinet severely restrict the unit’s
range?
No, the corrosion resistant NEMA 4X rated cabinet is not stainless steel but made from
fiberglass with stainless steel fittings (hinge, locking latch etc.) so it has very little effect on
the signal.
Mounting Inside Steel Enclosure
If the unit is mounted inside a steel electrical switchboard will the range be affected?
If using internal antennas yes, the range will be reduced if it is mounted inside a steel
enclosure. Whether the attenuation will be enough to prevent operation will depend on the
cabinet, distance to the other unit and all the other factors that affect range. If mounting inside
a steel enclosure an external antenna may extend the range significantly.
RFScada 8ADI-9DO/4ADI-5DO Manual Ver 3.6 Copyright ©2005 Data Delivery Devices LLC
Bartlesville OK Tel 918-335-3318
FAX 918-398-9990
Page - 116 –