Download Logix5000 Controllers Controller Major and Minor Faults
Transcript
Chapter 1 Major Faults The fault routine is added to the Power-Up Handler. 7. Double-click the newly-created routine to edit it. Programmatically Clear a Major Fault To clear a major fault that occurs during the execution of your project, see the following sections and complete these actions in the appropriate routine: • Creating a Data Type to Store Fault Information • Getting the Fault Type and Code • Checking for a Specific Fault • Clearing the Fault IMPORTANT Do not use fault routines to continually clear all faults on the controller. Program the fault routine to be selective in the types and number of faults cleared. IMPORTANT When a instruction errors due to a fault, for example, a COP with an indirect addressing programming error, the instruction is skipped and not executed. This occurs with all instructions. Creating a Data Type to Store Fault Information Logix5000 controllers store system information in objects. Unlike PLC-5 or SLC 500 controllers, there is no status file. • To access system information, you use a Get System Value (GSV) or Set System Value (SSV) instruction. • For status information about a program, you access the PROGRAM object. • For fault information, you access these attribute of the PROGRAM object. Attribute Data Type Instruction Description MajorFaultRecord DINT[11] GSV SSV Records major faults for this program. Specify the program name to determine which PROGRAM object you want. (Or specify THIS to access the PROGRAM object for the program that contains the GSV or SSV instruction.) 22 Rockwell Automation Publication 1756-PM014F-EN-P - September 2012