Download Powerware Ferrups Rackmount FER 850VA

Transcript
Section 300: Operation
This section will describe how FERRUPS works. We’ll discuss the meaning of the front panel lights and describe
how to use the control panel. We’ll also describe what the automatic system test does, what each alarm means,
what parameters do, and how to read the Alarm and Inverter Logs. Finally, we’ll see how to turn off FERRUPS.
301 Front Panel Lights
At the front of your FERRUPS is a panel with five lights (LEDs). These lights tell you several things about the
operating status of the FERRUPS.
Light (LED)
Color
What It Means When It’s
ON
What It Means When It’s
OFF
What It Means When It
Blinks
AC LINE
Green
FERRUPS is getting power
from the AC input power
source.
FERRUPS is not getting input
power; there is an outage, the
AC input breaker is tripped, or
you have unplugged the UPS.
Not applicable.
READY
Green
FERRUPS is ready to
provide backup power
from its batteries when
needed.
FERRUPS cannot provide
backup power; it may be in the
Line Condition Mode or the
Off Mode (see Section 302),
or its batteries may be
discharged, or it may be
running on battery power
(Inverter On mode).
You have just started the UPS;
the UPS is testing the batteries
as part of the automatic system
test (see Section 303); or, you
have started a timed shutdown
(Section 402).
CHARGING
Green
FERRUPS is charging the
batteries.
The battery charger is off;
batteries are at full charge.
Not applicable.
BATTERY
POWER
Yellow
FERRUPS is providing
power from its batteries; it
is in the Inverter Mode.
FERRUPS is providing
conditioned power from the
AC input power source, or
FERRUPS is off.
FERRUPS is testing the
inverter as part of the
automatic system test. (See
Section 303.)
ALARM
Red
FERRUPS is warning you
that an alarm exists. If you
have not silenced the alarm
beeper, you should be
hearing a code that tells
you what the problem is.
(See Section 304.) If you
have a control panel, an
alarm message appears on
its display.
No alarm exists.
Not applicable.
Page 10