Download MP-UM001 - Rockwell Automation
Transcript
Chapter 6 Configuration Guidelines Table 6 - Scaling Parameters Values User Unit Scaling Parameters (1) Distance Units for Ball Screw Linear Stages Millimeters Inches MPAS-xxxxxx-V05xxA MPAS-xxxxxx-V20xxA MPAS-xxxxxx-V05xxA MPAS-xxxxxx-V20xxA Velocity Label mm/s mm/s in./s in./s Velocity Scale 26214.4 6553.6 665845.76 166461.44 Position Label mm mm in. in. Position Scale 26214.4 6553.6 665845.76 166461.44 Acceleration Label mm/s/s mm/s/s in./s/s in./s/s Acceleration Scale 26214.4 6553.6 665845.76 166461.44 (1) User units are determined by the screw lead of the linear stage. The screw lead is defined in linear units of travel per revolution. For example, the travel per revolution of an MPAS-xxxxxx-V05xxA is 5 mm/ rev and that of an MPAS-xxxxxx-V20xxA is 20 mm/rev. MP-Series linear stages with a ball screw use a feedback device that provides 128 sin/cos cycles per revolution of the motor. The Ultra3000 drive interpolates this signal by an additional 1024, causing the maximum count per internal motor revolution of the linear stage to be 131,072 counts/rev. Table 7 - Direct Drive Linear Stage Distance Unit Settings User Unit Scaling Parameters 54 Distance Units Millimeters Inches Velocity Label mm/s in./s Velocity Scale 200 5080 Position Label mm in. Position Scale 200 5080 Acceleration Label mm/s/s in./s/s Acceleration Scale 200 5080 Rockwell Automation Publication MP-UM001D-EN-P - September 2013