6 Parameters
ptrn
Program Pattern 000
This parameter sets the type of control when using the simple program function.
Function
• If the program pattern is set to off, the simple program will not operate.
• If the program pattern is set to stop, the RUN/STOP status will change to STOP after the
soak time has expired. If the program pattern is set to cont, control will continue in RUN
status after the soak time has expired.
off
stop
cont
Setting
Setting range
Simple program function turned OFF
Go to STOP mode at end of program.
Continue in RUN mode at end of program.
Default
off
z Related Parameters
See
Program Start (Operation Level): Page 6-12
Soak Time Remain (Operation Level): Page 6-13
RUN/STOP (Operation Level) : Page 6-13
Soak Time (Adjustment Level): Page 6-31
Wait Band (Adjustment Level): Page 6-32
Soak Time Unit (Advanced Function Setting Level): Page 6-80
cp
c-cp
Function
Setting
Control Period (Heating)
Control Period (Cooling)
The cooling control output and heating control
output must be assigned to relay or voltage
outputs (for driving SSR).
The control must be set to 2-PID control.
For the Control Period (Cooling) parameter, the
control must be set to heating/cooling control.
• These parameters set the output periods. Set the control periods taking the control
characteristics and the electrical durability of the relay into consideration.
• For standard control, use the Control Period (Heating) parameter. The Control Period
(Cooling) parameter cannot be used.
• When the heating control output is a current output, the Control Period (Heating)
parameter cannot be used.
• For heating/cooling control, the control period can be set independently for heating and
cooling. The Control Period (Heating) parameter is used for the heating control output,
and the Control Period (Cooling) parameter is used for the cooling control output.
Parameter name
Control Period
(Heating)
Setting range
0.1, 0.2, 0.5, 1 to 99
Unit
Seconds
Control Period
(Cooling)
0.1, 0.2, 0.5, 1 to 99
Seconds
Default
20 for relay output
2 for voltage output (for driving SSR)
20 for relay output
2 for voltage output (for driving SSR)
z Related Parameters
See
6 - 46
PID ON/OFF (Initial Setting Level): Page 6-44
E5@C Digital Temperature Controllers User’s Manual (H174)