Download Digital Temperature Controllers User`s Manual
Transcript
6 Parameters ptrn Program Pattern 000 This parameter sets the type of control when using the simple program function. Function • If the program pattern is set to off, the simple program will not operate. • If the program pattern is set to stop, the RUN/STOP status will change to STOP after the soak time has expired. If the program pattern is set to cont, control will continue in RUN status after the soak time has expired. off stop cont Setting Setting range Simple program function turned OFF Go to STOP mode at end of program. Continue in RUN mode at end of program. Default off z Related Parameters See Program Start (Operation Level): Page 6-12 Soak Time Remain (Operation Level): Page 6-13 RUN/STOP (Operation Level) : Page 6-13 Soak Time (Adjustment Level): Page 6-31 Wait Band (Adjustment Level): Page 6-32 Soak Time Unit (Advanced Function Setting Level): Page 6-80 cp c-cp Function Setting Control Period (Heating) Control Period (Cooling) The cooling control output and heating control output must be assigned to relay or voltage outputs (for driving SSR). The control must be set to 2-PID control. For the Control Period (Cooling) parameter, the control must be set to heating/cooling control. • These parameters set the output periods. Set the control periods taking the control characteristics and the electrical durability of the relay into consideration. • For standard control, use the Control Period (Heating) parameter. The Control Period (Cooling) parameter cannot be used. • When the heating control output is a current output, the Control Period (Heating) parameter cannot be used. • For heating/cooling control, the control period can be set independently for heating and cooling. The Control Period (Heating) parameter is used for the heating control output, and the Control Period (Cooling) parameter is used for the cooling control output. Parameter name Control Period (Heating) Setting range 0.1, 0.2, 0.5, 1 to 99 Unit Seconds Control Period (Cooling) 0.1, 0.2, 0.5, 1 to 99 Seconds Default 20 for relay output 2 for voltage output (for driving SSR) 20 for relay output 2 for voltage output (for driving SSR) z Related Parameters See 6 - 46 PID ON/OFF (Initial Setting Level): Page 6-44 E5@C Digital Temperature Controllers User’s Manual (H174)