3 SPECIFICATION MELSEC-A 3.6.2 A/D conversion enable/prohibit specification (Address RWwm) (1) Set whether A/D conversion is enabled or disabled per channel. (2) By setting the unused channels to conversion prohibit, the sampling cycle can be shortened. Example) The sampling cycle when only channels 1 and 3 are set to A/D conversion enabled: 2 (Number of channels enabled) × 1ms (Conversion speed at one channel) = 2ms (3) Operation is performed according to the setting made for the leading edges of initial data setting request flag (RY(n+1)9). (4) The default setting is A/D conversion disable for all channels. b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 CH.4 CH.3 CH.2 CH.1 Ignored 3 - 14 1: Enable A/D conversion 0: Prohibit A/D conversion