Download Functional Description Manual

Transcript
5-44 Command Communication via Fieldbus
ECODRIVE03 FGP-03VRS
LED definition in module operation:
LED design
not assigned
H60
Module status
H61/MS
LED state
Definition
red
fatal error, replace card
red flashing
error can be cleared
green flashing
configuration error
green
ready OK
Explicit Message
query
H62
green (impulse)
in R/W via Explicit Message
Network status
H63/NS
off
not online
green flashing
online, but no connection to master
green
online master connected
red flashing
in I/O connection monitoring time
exceeded
red
critical connection error (doubled MACID or Bus-Off
red flashing
no synchronization of fieldbus module
with drive
green flashing
synchronization of fieldbus module with
drive established
off
no I/O connection
green
I/O connection OK, outputs valid and
input active
green flashing
outputs inactive (not sent by master)
red flashing
in I/O connection, monitoring time
exceeded
flashing regularly
Severe fieldbus module failure, switch
unit off and on.
internal
synchronization
H64
(Alive LED)
I/O status
Severe fieldbus
module failure
H65/IO
all LEDs
Fig. 5-53: Diagnosis LED for DeviceNet
DOK-ECODR3-FGP-03VRS**-FK02-EN-P