Download software manual - FDG Austria, DI Norbert Exler

Transcript
For a classical temperature controller (e.g. PID) only the
error in temperature is used as an input. The output o f
this PID-controller is the actual control action for a
control unit (e.g. heating system).
If a fuzzy temperature controller, represented by fuzz y
terms, is used, then it is necessary to convert (o r
transform) the current i nputs into fuzzy inputs by finding
the degrees of membership (fuzzy truth values) for al l
input membership functions.
This conversion from th e crisp input space into the fuzzy
input space is called fuzzification. The two inpu t
variables T and T are called linguistic variables, an d
each of these variables consist of a few membershi p
functions (fuzzy terms). The membership function s
(MFs) are assigned by the system designer (figure 48) ,
and are given labels such as cold, warm for T and
negative, zero, positive for
T. Each of these label s
represent a fuzzy set positioned in the operationa l
domain (universe of discourse) of possible crisp values.
In figure 48 the fuzzification process for input values of
T = 10°C and T = -2°C/time unit (shown on the x axis). The degree of membersh ip is the grade value at the
intersection the system input value makes with a
membership function.
FID - User´s guide
(c) 1993-97 FDG-Systems N. Exler
Page: 127