Humidity Offset
Errors in relative humidity (RH) readings are most likely not constant across all values of RH.
For example, if the sensor reads 35% when the true RH is 30% an offset of -5% would be correct.
This same sensor however is unlikely to show the same -5% offset when the true RH is 60% -- in
fact the error is likely to be less. As a result, the offset specified in the calibration table is
reduced as RH values reported by the sensor increase. This reduction is done in a smooth
(linear) fashion; the full offset is used at RH values of 30% (and below) and gradually reduced
to zero at a reported RH value equal to the RH maximum (discussed next).
Humidity Maximum Adjustment
After applying the humidity offset described above, the result will be adjusted again if it is
above 80%. The purpose of this offset is to get the reported reading up to a full 100% when the
air is saturated. This is done because the OS sensors never report RH values above 98%. To get
this up to 100%, a smoothly (linearly) increasing offset is added to RH readings – starting with
zero at 80% and increasing to a 2% offset when the reading is 98% -- this bumps it up just
enough to read a full 100%. However, to handle the case where your sensor may report less
than 98% when the air is saturated, the 98% limit is also selectable and is called “MAX” in the
calibration offset table.
The two corrections are applied in order – the humidity offset is computed and applied first.
The result is then adjusted for MAX if it is above 80%.
Multi-point Temperature & Humidity Calibration
Starting with WSDL beta version 4.2.1.4, a multi-point calibration table can be specified to
provide calibration offsets that vary according to the sensor reading (temperature or humidity).
For now this is a fledgling capability and users must hand-edit the project settings file to
enable them. Future beta versions of WSDL will provide more complete support for this
feature.
Errors in temperature and humidity may not be constant. For example the temperature may be
high by 2ºF when it is 50ºF, but the error might be -2ºF when it is 90ºF. You can supply some
number of temperature/offset data pairs. In this example there would be two pairs: {50,+2}
and {90,-2}. WSDL will apply the requested offset at the indicated temperature. For
temperatures in between the listed values, WSDL will draw a straight line between the two
points to determine the correction. The graph below shows this concept. For temperatures
outside the range of supplied values, the offset associated with the nearest value is used. In
the example one additional correction has been added of +3ºF when the sensor reading is 30ºF.
The straight lines drawn on the graph shows how WSDL interpolates correction between the
values in the table, and how it extends the first and last values without further interpolation.