PX2 SERIES - USER MANUAL
4 CONNECTION.
4.1
MAINS SUPPLY
L Before making any connection, make sure there is no voltage on the cables and this is cut off at the
corresponding electric switchboard.
The Extinguishing Control Panel can be fed from a voltage source of 110 to 250Vac, 50/60Hz.
The conduits and the mains wiring should be kept separate from the rest of the panel wiring.
For feeding in the power cables, the hole on the extreme right should be used.
Pass the cable through an appropriate cable gland for the cable type.
The connection to the three-position connector is carried out as shown in the following figure:
•
•
•
The phase cable (brown) should be connected to terminal L.
The neutral cable (blue or black) should be connected to terminal N.
The earth cable (green - yellow) should be connected to terminal T.
The connector has a 1-Amp fuse.
FUS
1A 250V~
L
N
POWER
SUPPLY
The supply for the fire control equipment must have a differential for independent protection with a safety
fuse of 230Vac / 5A or higher. The cross section of the power supply wiring must not be less than 0.75
mm2.
Ae-man-327-0.0 v1.0
11