Download PILESIM2
Transcript
SUPSI – DACD – ISAAC page 12 The mode that satisfies the greatest part of the heating and cooling demands is chosen. A schematic procedure to determine the operational mode is shown in Fig. 6.3. Note that the “resting mode” corresponds to the periods when the system is not used. No Heating demand ? Heating mode Resting mode No Yes Cooling demand ? No Yes Geocooling possible ? Yes Geocooling mode No Greater part of cooling demand covered with cooling machine ? Yes Cooling mode Fig. 6.3 Schematic presentation of the procedure followed to determine the operational mode. The heat pump performance coefficient and the cooling machine efficiency may depend on the temperature levels of the heat carrier fluid in the condenser and evaporator. The performance coefficient determines the heating power, with the help of the design electric power of the heat pump, set to a constant value. The design electric power determines the size of the heat pump and is fixed by the user. If the heating requirement is smaller, the heating power is decreased to match the heating requirement. As a result, the electric power consumed by the heat pump and the heat rate extracted at the evaporator are recalculated with the help of the performance coefficient. The heating power of the heat pump may also be reduced by the temperature constraint associated with the PILESIM2 user manual