Operator Workstation Technical Bulletin
21
Table 7: Messages that Can Occur during Direct Connection
Message
Explanation
Code Downloading
Metasys PMI code is being downloaded from the
workstation into the NCM.
Connected @ XXXX Baud Configured
The actual baud rate of connection is displayed in
message. XXXX may vary depending on the rate
and quality of the connection and can be
significantly less than the selected baud.
The workstation and NCM are successfully
connected at the specified baud rate. The workstation
is configured.
Connected @ XXXX Baud Unconfigured
The actual baud rate of connection is displayed in
message. XXXX may vary depending on the rate
and quality of the connection and can be
significantly less than the selected baud.
The workstation and NCM are successfully
connected at the specified baud rate. The workstation
is not configured.
Connecting to NC . . .
Physical connection and initialization of workstation is
successful. Connection is occurring.
Data Downloading
Data is being downloaded from the workstation into
the NCM.
Disconnected, Failed! Cannot Read NC NOVRAM
The workstation cannot read the network name from
the NCM’s NOVRAM.
Disconnected, Failed! Cannot Read NC State
Every 30 seconds the workstation attempts to read
the state of the NCM. This message indicates the
state cannot be read and the workstation has lost
communication from the NCM.
Disconnected, Failed! Global Data Failed
The process of synchronizing global data has failed.
Disconnected, Failed! Memory Error
An OWS memory error has occurred. Need system
reboot.
Disconnected, Failed! Network Name Invalid
The network name read from the NCM’s NOVRAM is
not defined in the workstation’s network database.
Disconnected, Failed! No Communication
NCM initialization failed or the workstation has
become physically disconnected from the NCM.
Disconnected, Failed! Port Not Enabled
OWS port initialization failed (hardware failure).
Disconnected, Retrying Configured
Connection between workstation and NCM is lost
because the NCM is rebooted or the cable is
unplugged. Workstation is retrying connection. This
message also occurs immediately before a code or
data download.
Global Data Updating
Global data is synchronizing between NCM and
workstation.
Initializing . . .
The initialization process is occurring. (The
workstation must be initialized before the connection
process can begin.)
NC Must Force Download
NCM must be reset by using the reset button on the
front, by manual command, or by cycling power on
the NCM.
NC Needs a Download
The NCM needs a download from the workstation.
NC Not Defined
NCM is not defined. Need to define the NCM in the
global database source file. See the Source File
Development section (LIT-630020) of the DDL
Programmer’s Manual for instructions.