Other Signal Modules
5.3.3
Freeze Function
The freeze function ”freezes” the module’s current encoder values. A frozen
encoder value is indicated by bit 31 being set (output range). The encoder value is
retained until the freeze function is terminated. The evaluation of the encoder
values can thus be event-dependent.
Prerequisite for Using the Freeze Function
The freeze function must be enabled and linked to the I0 and/or I1 digital inputs.
During parameterization you specify which I0/I1 digital inputs freeze the encoder
values.
With one digital input you can freeze one, two or three encoder values.
Terminating the Freeze State
The freeze state must be terminated separately for each encoder input. When the
user program acknowledges the transfer of the encoder value, bit 31 is deleted and
the encoder values are updated again.
You write the acknowledgment in the output address of the module with a set
acknowledgment bit by directly accessing the SM 338 (T PAB “xyz”).
Freezing is possible again as soon as you have deleted the acknowledgment bit in
the module’s output address.
S7-300 and M7-300 Programmable Controllers Module Specifications
EWA 4NEB 710 6067-02 01
5-11