Download E2 User Manual.book - Emerson Climate Technologies

Transcript
Output Device
Wire Output Board Set Fail-safe Dip
Switch to:
Contacts to:
Notes
Condenser Fan
(Single-Speed)
N.C.
N.C. (up)
To ensure condensing during network and power failure,
condenser fans should all be configured normally closed
(N.C.)
Condenser Fan
Relay (VariableSpeed)
N.C.
N.C. (up)
The fan should operate at 100% during loss of communication with E2.
Dampers (Evap.
only)
N.C.
N.C. (up)
Dampers should be open during communication loss
(N.C.).
Evaporator
Pumps (Evap.
only)
N.C. (see note)
N.C. (see note)
Some condensers have dual pumps that cycle at even
intervals. One pump should be wired N.C. and the other
N.O., so that only one pump runs during communication
loss.
Variable-Speed
Fan Output (to
inverter)
None (analog
point)
None (analog
point)
This 4AO or 8IO analog point sends the 0-100% fan
speed signal to the inverter.
Table 11-4 - Suction Group Outputs
11.3 Standard Circuits
Refrigerated cases that do not use case controllers are
controlled by Standard Circuit applications. In a Standard
Circuit application, the E2 is responsible for all case monitoring and control; it uses the RS485 I/O Network to both
gather case temperature inputs and activate or deactivate
the liquid line solenoids, defrost modes, and fans. Also,
circuits that use ESR8s and MultiFlex ESRs are controlled
using Standard Circuits.
NOTE: Do not set up a Standard Circuit application for a case that uses a CC-100 or CCB
case controller. These cases must use Case Circuit Control applications (see Section 11.4, Case Control Circuits).
11.3.1 Refrigeration Control
A Standard Circuit application may apply one of four
different control methods to a case circuit: the Temperature Monitor method, the Temperature Control method,
and the Line Up(ESR)/Defrost method, and the
Lineup(MFESR)/Defrost method.
11.3.1.1
Temperature Monitor
The Temperature Monitor method does not control
case temperature. The application will read and record
case temperature inputs, but it will not make any attempt
to control temperature. The application will still initiate
and control defrost, cycle fans, and perform other necessary functions.
11.3.1.2
Temperature Control
A Standard Circuit application using the Temperature
Control method will pulse the refrigeration liquid line
solenoid OPEN and CLOSED so as to control the case
temperature to the user-defined setpoint. The application
monitors up to six different temperature sensors in the circuit and combines them into a single value that is compared to the setpoint.
11.3.1.3
Line Up(ESR)/Defrost
In Line Up ESR, circuit temperature is controlled by
an electronic evaporator pressure regulator (EEPR). The
EEPR is controlled by a PID algorithm that steps the valve
open from 0% to 100% based on how far away the circuit
11-6 • E2 RX/BX/CX I&O Manual
026-1610 Rev 17 10-JUL-2014