Download E2 User Manual.book - Emerson Climate Technologies
Transcript
Output Device Wire Output Board Set Fail-safe Dip Switch to: Contacts to: Notes Condenser Fan (Single-Speed) N.C. N.C. (up) To ensure condensing during network and power failure, condenser fans should all be configured normally closed (N.C.) Condenser Fan Relay (VariableSpeed) N.C. N.C. (up) The fan should operate at 100% during loss of communication with E2. Dampers (Evap. only) N.C. N.C. (up) Dampers should be open during communication loss (N.C.). Evaporator Pumps (Evap. only) N.C. (see note) N.C. (see note) Some condensers have dual pumps that cycle at even intervals. One pump should be wired N.C. and the other N.O., so that only one pump runs during communication loss. Variable-Speed Fan Output (to inverter) None (analog point) None (analog point) This 4AO or 8IO analog point sends the 0-100% fan speed signal to the inverter. Table 11-4 - Suction Group Outputs 11.3 Standard Circuits Refrigerated cases that do not use case controllers are controlled by Standard Circuit applications. In a Standard Circuit application, the E2 is responsible for all case monitoring and control; it uses the RS485 I/O Network to both gather case temperature inputs and activate or deactivate the liquid line solenoids, defrost modes, and fans. Also, circuits that use ESR8s and MultiFlex ESRs are controlled using Standard Circuits. NOTE: Do not set up a Standard Circuit application for a case that uses a CC-100 or CCB case controller. These cases must use Case Circuit Control applications (see Section 11.4, Case Control Circuits). 11.3.1 Refrigeration Control A Standard Circuit application may apply one of four different control methods to a case circuit: the Temperature Monitor method, the Temperature Control method, and the Line Up(ESR)/Defrost method, and the Lineup(MFESR)/Defrost method. 11.3.1.1 Temperature Monitor The Temperature Monitor method does not control case temperature. The application will read and record case temperature inputs, but it will not make any attempt to control temperature. The application will still initiate and control defrost, cycle fans, and perform other necessary functions. 11.3.1.2 Temperature Control A Standard Circuit application using the Temperature Control method will pulse the refrigeration liquid line solenoid OPEN and CLOSED so as to control the case temperature to the user-defined setpoint. The application monitors up to six different temperature sensors in the circuit and combines them into a single value that is compared to the setpoint. 11.3.1.3 Line Up(ESR)/Defrost In Line Up ESR, circuit temperature is controlled by an electronic evaporator pressure regulator (EEPR). The EEPR is controlled by a PID algorithm that steps the valve open from 0% to 100% based on how far away the circuit 11-6 • E2 RX/BX/CX I&O Manual 026-1610 Rev 17 10-JUL-2014