C441Q/S PROFIBUS Communication Module
C440 Overload Supported Configuration Modules, continued
I/O
Size (in bytes)
Configuration Modules
Notes
Input
2
C440 RMS Current I1
Scaling: value in 0.01 amps
Input
2
C440 RMS Current I2
Scaling: value in 0.01 amps
Input
2
C440 RMS Current I3
Scaling: value in 0.01 amps
Input
2
C440 RMS Current Ave
Scaling: value in 0.01 amps
Input
1
C440 FLA Current %
Presents the average current as a percent of the FLA setting
Input
1
C440 Used Thermal Pile %
Present thermal capacity (100% equates to a trip condition)
Input
2
C440 FLA Setting
The present FLA setting (the potentiometer selects this value)
Input
1
C440 Overload Trip class
The present FLA trip class
Input
1
C440 Phase Imbalance %
Percent of measured phase imbalance
Input
2
C440 GND Fault Current
Scaling: value in 0.01 amps
Input
1
C440 GND Fault %
Percent of ground fault measured: GF% = GFC/([0.5]*FLA)
Input
2
C440 Temperature
The temperature as seen by the microcontroller (accuracy ~ 10%)
Input
2
C440 Line Frequency
The line frequency measured by the device (the frequency is displayed in deciHz)
Input
2
C440 Feature Status
Bit Feature
01 = Class Index
00 = Class 10a
01 = Class 10
10 = Class 20
11 = Class 30
2 = Phase loss/imbalance enabled
3 = Ground fault enabled
4 = Auto reset enabled
5 = Remote reset active
8 = DIP switch position 0
9 = DIP switch position 1
10 = DIP switch position 2
11 = DIP switch position 3
12–15 = Reserved