Download FERCS10, week 48/2009
Transcript
Parameter explanation: • • • • • name output new name time pulse length in seconds type what mode output follows o normal o pulse o system o alarm o sensor or zone name connected to the FERCS10 system on_value limit when output is set on when output follows a sensor off_value limit when output is set off when output follows a sensor Parameter default values: • • • • • name outputX time 0 type normal on_value 0 off_value 0 Examples: • • • • • • User wants to modify information off an output called output1: name is changed to lock, type to pulse mode and pulse time to 5 seconds o control set output1, name=lock, type=pulse, time=5 User wants to modify information off an output called output2: type is changed to normal mode o control set output2, type=normal User wants to modify information off an output called lock: name is changed to indicator and type to system mode o control set lock, name=indicator, type=system User wants to modify information off an output called output2: type is changed to alarm mode o control set output2, type=alarm User wants to modify information off an output called output1: type is changed to zone mode following a zone called flood o control set output1, type=flood User wants to modify information off an output called output2: type is changed to sensor mode following a sensor called temperature, output is set on when temperature is 28.5°C or more and set off when temperature is 20°C or less o control set output2, type=temperature, on_value=28.5, off_value=20 56