Download PowerFlex 700 AC Drives

Transcript
Parameter Name & Description
See page 3-2 for symbol descriptions
Torque Proving
610 [Brk Alarm Travel]
Values
Default:
3-61
Related
No.
Group
File
Programming and Parameters
1.0 Revs
Sets the number of motor shaft
Min/Max: 0.0/1000.0 Revs
revolutions allowed during the brake
Units:
0.1 Revs
slippage test. Drive torque is reduced to
check for brake slippage. When slippage
occurs, the drive allows this number of
motor shaft revolutions before regaining
control. Not used in Encoderless
TorqProve mode.
Default: 10.0%
611 [MicroPos Scale%]
Sets the percent of speed reference to be Min/Max: 0.1/100.0%
used when micropositioning has been
Units:
0.1%
selected in [TorqProve Cnfg]. Bit 2 of
[TorqProve Cnfg], parameter 600
determines if the motor needs to come to
a stop before this setting will take effect.
Read Only
612 [Torq Prove Sts]
361
thru
366
600
APPLICATIONS
Re
fL
Lo oadL
ad im
Br Tes td
ak tA
Br e Se ctv
kS t
Mi lipA
cr la
De oPos rm
ce A
En lLim ctv
dL Ac
im tv
itA
ctv
Displays the status bits for TorqProve.
x x x x x x x x x 0 0 0 0 0 0 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1 = Enabled
0 = Disabled
x = Reserved
Bit #
631 [Rod Load Torque]
Default:
Read Only
Oil Well Pump
Displays the load side torque. [Alarm
Min/Max: 0.00/32000.00 FtLb
Config 1], parameter 259, bit 19 must be Units:
0.01 FtLb
enabled to activate this display.
Default: 0.00 FtLb
632 [TorqAlarm Level]
Sets the level at which the Torque Alarm Min/Max: 0.00/5000.00 FtLb
becomes active. Note: only active with
Units:
0.01 FtLb
PC pump applications (see param. 641).
Default: 0
“No Action”
633 [TorqAlarm Action]
Sets the drive action when the Torque
Options:
Alarm is exceeded. Note: only active with
PC pump applications (see param. 641).
Default:
634 [TorqAlarm Dwell]
Sets the time that the torque must
Min/Max:
exceed [TorqAlarm Level] before
Units:
[TorqAlarm Action] takes place. Note:
only active with PC pump applications
(see param. 641).
Default:
635 [TorqAlrm Timeout]
0
1
“No Action”
“Goto Preset1”
0.0 Secs
0.0/60.0 Secs
0.1 Secs
0.0 Secs
Sets the amount of time a Torque Alarm Min/Max: 0.0/600.0 Secs
can be active until timeout action begins. Units:
0.1 Secs
Note: only active with PC pump
applications (see param. 641).
Publication 20B-UM002C-EN-P