Download PowerFlex 700 AC Drives
Transcript
Parameter Name & Description See page 3-2 for symbol descriptions Torque Proving 610 [Brk Alarm Travel] Values Default: 3-61 Related No. Group File Programming and Parameters 1.0 Revs Sets the number of motor shaft Min/Max: 0.0/1000.0 Revs revolutions allowed during the brake Units: 0.1 Revs slippage test. Drive torque is reduced to check for brake slippage. When slippage occurs, the drive allows this number of motor shaft revolutions before regaining control. Not used in Encoderless TorqProve mode. Default: 10.0% 611 [MicroPos Scale%] Sets the percent of speed reference to be Min/Max: 0.1/100.0% used when micropositioning has been Units: 0.1% selected in [TorqProve Cnfg]. Bit 2 of [TorqProve Cnfg], parameter 600 determines if the motor needs to come to a stop before this setting will take effect. Read Only 612 [Torq Prove Sts] 361 thru 366 600 APPLICATIONS Re fL Lo oadL ad im Br Tes td ak tA Br e Se ctv kS t Mi lipA cr la De oPos rm ce A En lLim ctv dL Ac im tv itA ctv Displays the status bits for TorqProve. x x x x x x x x x 0 0 0 0 0 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 1 = Enabled 0 = Disabled x = Reserved Bit # 631 [Rod Load Torque] Default: Read Only Oil Well Pump Displays the load side torque. [Alarm Min/Max: 0.00/32000.00 FtLb Config 1], parameter 259, bit 19 must be Units: 0.01 FtLb enabled to activate this display. Default: 0.00 FtLb 632 [TorqAlarm Level] Sets the level at which the Torque Alarm Min/Max: 0.00/5000.00 FtLb becomes active. Note: only active with Units: 0.01 FtLb PC pump applications (see param. 641). Default: 0 “No Action” 633 [TorqAlarm Action] Sets the drive action when the Torque Options: Alarm is exceeded. Note: only active with PC pump applications (see param. 641). Default: 634 [TorqAlarm Dwell] Sets the time that the torque must Min/Max: exceed [TorqAlarm Level] before Units: [TorqAlarm Action] takes place. Note: only active with PC pump applications (see param. 641). Default: 635 [TorqAlrm Timeout] 0 1 “No Action” “Goto Preset1” 0.0 Secs 0.0/60.0 Secs 0.1 Secs 0.0 Secs Sets the amount of time a Torque Alarm Min/Max: 0.0/600.0 Secs can be active until timeout action begins. Units: 0.1 Secs Note: only active with PC pump applications (see param. 641). Publication 20B-UM002C-EN-P