Integral
indicator
HART communicator
display
AL.87
FLG. HI
FT high alarm
AL.87
FLG. LO
FT low alarm
AL.88
INVR.DP
9-12
<9. Maintenance>
Invalid Ref DP
Cause
Flange temperature
exceeds a preset upper
limit.
Flange temperature is
below a preset lower
limit.
4-20mA Output
operation during error
Countermeasure
It depends on the Diag Out
Option setting.
Check the heater
failure.
Off: Continue to operate
and output.
Burnout:Outputs AO
upper limit or AO lower
limit.
Fall back:Outputs Diag
Out Fixed Val.
Continue to operate and
output.
Check the capsule
temp. and Amplifier
temp.
Status
group
Adjust Flg Temp
Coef.
Differential pressure/
pressure fluctuation
does not reach the
reference level required
to blockage detection
so that no blockage
detection is carried out.
Low-pressure-side
fluctuation does not
reach the reference
fluctuation level required
to blockage detection.
High-pressure-side
fluctuation does not reach
the reference fluctuation
level required to blockage
detection.
BlkF can not be used for
blockage detection for
some reasons.
Appointed the diagnosis
range outside.
B Blocking (both-side
It depends on the Diag Out
blockage) is detected.
Option setting.
High-pressure-side
Off: Continue to operate
blockage is detected.
and output.
Low-pressure-side
Burnout: Outputs AO
blockage is detected.
upper limit or AO lower
Pressure fluctuation
limit.
amplitude of highFall back: Outputs Diag
pressure side is large.
Out Fixed Val.
Pressure fluctuation
amplitude of lowpressure side is large.
A Blocking (single-side
blockage) is detected.
Check process
condition.
9
AL.88
INVR.SL
Invalid Ref SPL
AL.88
INVR.SH
Invalid Ref SPH
AL.88
INVR.F
Invalid Ref F
AL.89
ILBD.OV
AL.89
B BLK
AL.89
H BLK
AL.89
L BLK
AL.89
H LRG
ILBD over range
AL.89
L LRG
Large Fluct L
AL.89
A BLK
A Blocking
AL. 90
SIM
Simulate Mode
Under Simulation Mode.
Simulate input output.
Check Simulation
Mode.
5
ET Fixed Mode
Under Temperature Fix
Mode. PV is ET
Temp. Output Fix at 4mA.
Leave from
Temperature Fix
Mode.
7
—
B Blocking
H Side Blocking
L Side Blocking
Large Fluct H
Check process
condition.
Check process
condition.
10