Download EJX910A and EJX930A Multivariable Transmitters
Transcript
Integral indicator HART communicator display AL.87 FLG. HI FT high alarm AL.87 FLG. LO FT low alarm AL.88 INVR.DP 9-12 <9. Maintenance> Invalid Ref DP Cause Flange temperature exceeds a preset upper limit. Flange temperature is below a preset lower limit. 4-20mA Output operation during error Countermeasure It depends on the Diag Out Option setting. Check the heater failure. Off: Continue to operate and output. Burnout:Outputs AO upper limit or AO lower limit. Fall back:Outputs Diag Out Fixed Val. Continue to operate and output. Check the capsule temp. and Amplifier temp. Status group Adjust Flg Temp Coef. Differential pressure/ pressure fluctuation does not reach the reference level required to blockage detection so that no blockage detection is carried out. Low-pressure-side fluctuation does not reach the reference fluctuation level required to blockage detection. High-pressure-side fluctuation does not reach the reference fluctuation level required to blockage detection. BlkF can not be used for blockage detection for some reasons. Appointed the diagnosis range outside. B Blocking (both-side It depends on the Diag Out blockage) is detected. Option setting. High-pressure-side Off: Continue to operate blockage is detected. and output. Low-pressure-side Burnout: Outputs AO blockage is detected. upper limit or AO lower Pressure fluctuation limit. amplitude of highFall back: Outputs Diag pressure side is large. Out Fixed Val. Pressure fluctuation amplitude of lowpressure side is large. A Blocking (single-side blockage) is detected. Check process condition. 9 AL.88 INVR.SL Invalid Ref SPL AL.88 INVR.SH Invalid Ref SPH AL.88 INVR.F Invalid Ref F AL.89 ILBD.OV AL.89 B BLK AL.89 H BLK AL.89 L BLK AL.89 H LRG ILBD over range AL.89 L LRG Large Fluct L AL.89 A BLK A Blocking AL. 90 SIM Simulate Mode Under Simulation Mode. Simulate input output. Check Simulation Mode. 5 ET Fixed Mode Under Temperature Fix Mode. PV is ET Temp. Output Fix at 4mA. Leave from Temperature Fix Mode. 7 — B Blocking H Side Blocking L Side Blocking Large Fluct H Check process condition. Check process condition. 10 IM 01C25R01-01E