Download Manual
Transcript
Parameter page 3 The displayed value for the nominal voltage is: 0 In a 4-conductor grid = 230V conductor-earth voltage 0 In a 3-conductor grid = 100V conductor-conductor voltage, multiplied by the conversion factor The % value is used to set the reference voltage at a different value to the nominal voltage. Example 1: 20,000V * 105% = Reference voltage of 21,000V. This is the reference value for all trigger thresholds as well as Power Quality events. Example 2: 500V grid (conductor-conductor) 230V * 125% = 287.5V (conductor-earth) Parameter page 4 Rated current All trigger thresholds for the current refer to the set nominal current. The nominal current for the system should be entered here. Reference channel defines the measuring channel for frequency measurements and grid synchronisation. Operation of the PQI-DA smart LEREF "Verzeichnis Ueberschrift" \* MERGEFORMAT Index Page 37