8.2 FLAMEPROOF CERTIFICATION The S231f+, S241f+, S251f+, S261f+ and S271f+ are designed to comply with EN 60079-0 : 2006 and EN 60079-1 : 2004 for flameproof enclosures. They are certified ATEX code: II 2 G Cenelec code: Ex d IIC T6 or T5 (-20°C Ta +80°C) Under ATEX certificate number Baseefa02ATEX0185. This certification shows the S200f+ detectors are certified ‘flameproof’, meeting the requirements of EN 60079-1 : 2004. They are classified as suitable for zones 1 and 2 areas over an ambient temperature range -20°C to +80°C for temperature class T5 gasses and for temperature class T6 gasses. The certified labels for the S241f+ and S261f+ are shown in Fig. C-15 and C-16. The labels for the S231f+, S251f+ and S271f+ are not shown as apart from the model number they are identical to the S241f+. The S231f+, S241f+, 261f+ and S271f+ are also IECEx certified: IECEx BAS 05.0056 Ex d IIC T6 or T5 (-20°C Ta +60°C) This certificate shows the S200f+ detectors are certified, meeting the requirements of EN 600790. They are certified as suitable for Zones 1 and 2 over temperature range -20°C to +60°C for temperature class T5 gasses and -20°C to +40°C for temperature class T6 gasses. 8.3 CONSTRUCTION PRODUCTS REGULATION The S200+ range of flame detectors comply with and are manufactured to the requirements of the Construction Products Regulation – see “CPR INFORMATION” on page 34. The detectors carry the CE mark. 32