These drive parameter configure the drive digital inputs to receive digital commands from
the Elevator Controls V900 Non-PVF controller.
Parameter
di. 0 Input source configuration
A4.2.8
Section Intentionally Left Blank
A4.2.9
Motor Parameters
EC Setting
NPn
Units
Sinking inputs
These drive parameters configure the drive for the hoist motor.
Parameter
LF.12 Rated Motor Current
LF.13 Rated Motor Frequency, per motor name plate
LF.14 Rated Motor Voltage
LF.17 Rated Motor Torque, per motor name plate
LF.18 Motor Stator Resistance, per motor name
plate
LF.19 Motor Leakage Inductance
EC Setting
(*)
(*)
(*)
(*)
(*)
Units
Amps
Hz
Volts
Lb ft
Ohms
(*)
Mili-Henries
NOTE: The inductance listed on the motor manufacturer’s data sheet will have to be
multiplied by two if it is listed per motor phase.
A4.2.10 Acceleration Deceleration and “S” Curve Parameters
These drive parameters configure the speed profile the drive will generate to start, accelerate,
decelerate and stop the car. Refer to Section 4.6 of this manual for configuration and speed
profile details.
Parameter #
EC Setting
Units
LF.50 Starting Jerk
3.0 (*)
Ft/Sec Cube
LF.51 Acceleration
2.0o 3.0 (*)
Ft/Sec Square
LF.52 Roll Into Constant Speed Jerk
3.0 to 4.0 (*) Ft/Sec Cube
LF.53 Deceleration Jerk
3.25 to 4.25 (*) Ft/Sec Cube
LF.54 Deceleration
1.8 to 3.5 (*) Ft/Sec Square
LF.55 Final Approach Jerk
2.5 (*)
Ft/Sec Cube
LF.56 Leveling to Final Stop Jerk
2.0 (*)
Ft/Sec Cube
A4.3 Overspeed Using the Drive to Drive the Hoist Motor
The drive unit can be configured to run the hoist motor at a frequency larger than the hoist
motor base input frequency to create an overspeed condition as follows:
e. Place the car on Test mode.
f. Take the car to terminal Landing.
g.Increment Program parameter LF.23 to next value.
h. Place a Car Call several floors above/ below floor to allow car to attain overspeed.
Model V900 Non-PVF Prodigy & Standard Traction Controller Installation & Adjustment Manual
98