4-28 Module Data, Status, and Channel Configuration for the Output Modules Table 4.16 1769-OF8V Output Range/Types and Output Data Formats Output Data Format Output Range/Type Total Counts in Full Scale Number of Counts for Every 1% of Ramp Rate Real Units/Second for Every 1% of Ramp Rate 100 0.2V/s Percent of Full Scale -10…+10V 10000 0…5V 0.05V/s 0…10V 0.1V/s 1…5V 0.04V/s Ramping only takes place, if configured, when the output is being commanded to go to a fault state. Ramping is not done in normal run operation. The ramp rate values are entered in the Configuration Data file and are accepted as valid only if: • The number of counts entered for a channel’s ramp rate is greater than or equal to a minimum of 1% of the total number of full scale counts for the channel’s selected data format (see Table 4.14 and Table 4.15 for minimum values). OR • The number of counts entered for a channel’s ramp rate may be equal to 0 if ramping is not enabled for the channel. Hold for Initialization Hold for Initialization causes outputs to hold present state until the value commanded by the controller matches the value held by the module providing a bumpless transfer. If Hold for Initialization is selected, outputs hold if any of these three conditions occur: • initial connection is established after power-up • new connection is established after a communications fault occurs • transition to Run Mode from Program state The Output Held bit (see the Input Data file) for a channel indicates that the channel is holding. Publication 1769-UM002B-EN-P - July 2005