CHAPTER 7: COMMISSIONINGCOMMISSIONING
Z Provided that the operate times are not scattered over a wide range, it
may be desirable to repeat this test several times and average the results.
Z If there is a wide scatter, verify the test setup and ensure the signal
source behaves in a consistent manner.
Note
The blocking from logic input, if enabled, can be tested as described in earlier tests for
other elements.
7.5.17.3 Underfrequency 2
Z Disable all protection functions except the underfrequency 2 function.
Z Verify that settings match in-service requirements. Enter/modify
settings and logic in the S4 ELEMENTS ZV FREQUENCY ZV
UNDERFREQUENCY 2 setpoints menu.
Z Repeat the appropriate steps of Underfrequency 1 on page 7–44 for this
element.
Z Compare the results to the settings for the underfrequency 2 element.
7.5.17.4 Overfrequency
Z Disable all protection functions except overfrequency.
Z Verify that settings match in-service requirements.
Overfrequency settings are modified in the S4 ELEMENTS ZV
FREQUENCY ZV OVERFREQUENCY settings menu.
Voltage input function (voltage input enabled):
Using the variable-frequency voltage/current source connected to terminals C11 and C12
for the voltage signal and H1 and G1 for the current signal,
Z Set the frequency to 60.00 Hz (or 50.00 Hz) and the voltage amplitude
to the rated VT secondary voltage.
Z Set the current amplitude to rated CT secondary.
Z Monitor the appropriate trip and auxiliary relays.
Z Reset all alarms and indications on the relay.
The 745 display should remain unchanged with no trip indications.
Z Slowly increase the frequency until the output relay(s) operate.
Z Check that the frequency at which operation took place is the selected
frequency setting.
Z As the frequency is varied, verify that the A2 METERING ZV
FREQUENCY Z SYSTEM FREQUENCY actual value indicates the correct
value of system frequency.
Z Slowly reduce the voltage.
Z Note the voltage at which the output relay(s) reset.
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
7–47