This chapter describes examples of setting PV input types, control output types.
Carrying out settings described herein allows you to perform basic control. Refer to
examples of various settings to understand how to set parameters required. Refer to
“6.1 Parameter Map” for an easy to understand explanation of setting various
parameters. If you cannot remember how to carry out an operation during setting,
press the DISP key no more than four times. This brings you to the display (operating
display) that appears at power-on. After carrying out the settings described here,
create programs in “3. Programming.”
Setup Procedure
Denotes a step that must always be followed.
Power-on
Denotes a step that should be followed as necessary.
Set UP mode “6”
(Factory-set to Single-loop Control “UP mode 1.”)
See “2.2 Setting UP mode (Setting First at Power-on)”
or “2.3 Changing UP mode.”
Set PV input
(Factory-set to ; PV input 1 is “not configured”, PV input 2 is “standard signal (1-5 V DC).”)
See “2.4 Setting PV Input 1 and PV Input 2 Types.”
Set Controlled PV
Input Range
See “2.5 Setting Controlled PV Input Range.”
Set the control
output.
(Factory-set to “Time Proportional Relay Output.”)
See “2.6 Setting Control Output Type.”
Be sure to follow this
step whenever a chang of setting
is made to the UP mode or
PV input type.
See “2.7 Initializing Parameters.”
Initialize
parameters.
Set setup
parameters.
Set PV Switching
Methods
See “2.8 Setting PV Switching Methods.”
No
Switching
input with contact
input
Yes
Set Input Switching
PV Range
See “2.9 Setting Input Switching PV Range.”
Set operating
parameters.
Set program
patterns.
See “3. Programming.”
Controller operation
IM 05E01B02-46E
1st Edition : May 31,2000-00