Download Cat 4979.book

Transcript
16
Figure 1 Control Drawing 911-V1
A
B
C
D
6
5
4
8
TABLE 2
TABLE 1
7
REF. TABLE 1
OR 2 FOR P/N
AREA VELOCITY
PROBE
6
25 FT - 100 FT MAX
7.6m - 30.5m
INTEGRAL
IN LINE VENT
ASSEMBLY
5
THIS DRAWING
PRIOR TO CHANGING
APPROVAL REQUIRED
REGULATORY AGENCY
P/N 5150
MODEL 911
FLOWMETER
L
REV
MAX LENGTH
150 FT.
MAX LENGTH
150 FT.
P/N 4274
SAMPLER
OPTO-ISOLATED
INTERFACE
RS-232
OPTO-ISOLATED
INTERFACE
P/N 5254200
-ORP/N 5254100
-OR-
RS-232
OPTO-ISOLATED
INTERFACE
P/N 4738
-ORP/N 4087
NONHAZARDOUS (CLASSIFIED)
LOCATION
3
10 FT
3.1 m
NONCLASSIFIED
SAMPLER
6.56 FT
2.0 m
3-5v DC
TO SIGMA
1000
TO COMPUTER
Jeff Archer
10 FT
3.1 m
3-5v DC
APPROVED
1
09-561
REVISION
DESCRIPTION
2
MATERIAL
4
3
DO NOT SCALE DRAWING
INTERPRET GEOMETRIC
TOLERANCING PER:
ANSI Y14.5M 1994
DIMENSIONS ARE IN INCHES
TOLERANCES:
.X
= .03
.XX
= .01
.XXX
= .005
ANGLES = .25
UNLESS OTHERWISE SPECIFIED:
S.D
S.D
ENGINEER
2
HACH COMPANY
SCALE: 1:2 WEIGHT:
1
911-V1
L
REV
SHEET 1 OF 1
DRAWING, CONTROL
911 BASE
5600 LINDBERGH DR.
LOVELAND, CO. 80539
SIZE DWG. NO.
B
THIRD ANGLE PROJECTION TITLE:
DATE
12/2/05
NAME
DRAWN
NOTICE--HACH COMPANY CLAIMS PROPIETARY RIGHTS IN THE INFORMATION DISCLOSED ON THIS DRAWING. IT IS ISSUED
IN CONFIDENCE FOR ENGINEERING INFORMATION ONLY AND MAY NOT, IN WHOLE OR IN PART, BE USED TO MANFACTURE
ANYTHING, WHETHER OR NOT SHOWN HEREON, REPRODUCED OR DISCLOSED TO ANYONE WITHOUT DIRECT PERMISSION
FROM HACH COMPANY.
HAZARDOUS (CLASSIFIED) LOCATION
CLASS 1, DIV. 1, GROUP C,D
WIRING METHODS MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, ANSI/NFPA 70, ARTICLE 504,
CANADIAN ELECTRIC CODE, C22.1-94, SECTION 18 AND ANSI/ISA RP 12.6
7
2.
8
IF THE ELECTRICAL PARAMETERS OF THE CABLE ARE UNKNOWN, THE FOLLOWING DEFAULT VALUES MAY BE USED.
CAPACITANCE - .2nf/METER, INDUCTANCE - 1uh/METER
1.
A
B
C
D
Meter Installation