Transcript
Chapter 7 Troubleshooting Table 29 - Synchronizing Symptom Most Likely Cause Diagnostic Action Corrective Action No close indication from CGCM unit (cont.) Voltage not matched Observe voltage match tag during synchronization If voltage match indicated, check close command tag. If no voltage match indicated, check voltage match error Observe voltage error, generator voltage, and selected bus voltage reported by CGCM unit during synchronization If no voltage error is reported by CGCM unit correct wiring and verify appropriate Synchronization mode is active If voltage error is reported, verify voltage setpoint to CGCM unit is being adjusted appropriately to provide voltage correction Close indication from CGCM unit when sync parameters not met Configuration errors Observe VT and Bus offset configuration parameters to verify they reflect the desired/expected VT wiring Correct configuration to match expected VT wiring Wiring errors Adjust manually such that test equipment (reference) indicates synchronism, the observe diagnostics above. This information can be used to determine most likely wiring error. Voltage not matched, verify PT wiring and VT ratios are correct. Phase or frequency not matched; verify phase rotation and polarity of VT wiring Correct VT wiring Metering If there is a difference between the metering data reported by the CGCM unit and a reference meter, verify the metering used to determine CGCM unit malfunction is being correctly used and in calibration. Table 30 - Metering Symptom Most Likely Cause Diagnostic Action Corrective Action Voltage does not read correctly Configuration errors Observe VT configuration and rotation parameters and to verify they reflect desired/expected VT wiring Correct configuration to match expected VT wiring Wiring errors Observe each LL, phase, average Correct phase rotation, polarity, voltage, and rotation indication. grounding, or fusing as applicable Indicated rotation matches configured rotation. LL voltage (and LN if applicable) indicated if all low or high indicate ratio error, if one or two are low or high indicate polarity, grounding, or disconnection Measure signal at CGCM unit terminals 162 Rockwell Automation Publication 1407-UM001H-EN-P - November 2014 If voltage indicated corresponds to measured value, correct VT wiring. If voltage indicated does not correspond to measured voltage, see configuration errors. If configuration is correct, replace CGCM unit