Chapter 8 - Trouble Shooting & Repair
door of the control section are closed.
Danger: Never work on a powered ACS 1000. The main circuit breaker
and the input isolators must always be opened and locked in “OPEN” position. Do not access the main power circuit nor the motor as long as the
system is not grounded.
When switching off the mains, always allow the intermediate circuit capacitors to discharge before grounding and starting work on the frequency
converter, the motor or the motor cable.
The ACS 1000 and adjoining equipment must be properly grounded
and the auxiliary supply voltage must be switched off prior to
starting with any work.
Danger: Some loads may apply a mechanical torque on the motor shaft!
If the motor can rotate due to such a load, always disconnect, short-circuit
or mechanically block the motor before you start work.
Danger: There can be dangerous voltages inside the ACS 1000 from external control circuits (measurement inputs from PT’s etc.) even if the
ACS 1000 mains power and auxiliary power are shut off. Take appropriate
measures when working with the unit, i.e deenergize and disconnect all
such external devices (auxiliary supply, heaters, coolers, I/O-interfaces)
before you start work.
Danger: The grounding isolator may become ineffective if the power circuit is opened. The main circuit breaker and the input isolators must always be opened and locked in “OPEN” position. Any external ground
switch must be closed and locked.
Prior to start working on the ACS 1000 the general safety regulations in
Chapter 1 - Safety Instructions must be read and understood.
ABB Industrie AG declines all liability for any possible damage resulting
from failure or negligence to observe these warnings.
Alarm and Fault
Handling
If a disturbance occurs anywhere in the converter or in related equipment,
it will be indicated with an error message on the CDP 312 control panel or,
as alternative, on the DriveWindow error display.
Two error message levels are used with the ACS 1000:
• Fault: a fault is initiated by a serious disturbance in the converter or in
related equipment (transformer, motor etc.) and always implies a converter trip. The converter will remain in tripped state (with the exception
of a few faults where the converter will resume operation automatically
after the disturbance has disappeared).
8-2 (of 38)
3BHS102769
ACS 1000 User’s Manual, Rev. C