Download Table of Contents
Transcript
Chapter 8 - Trouble Shooting & Repair door of the control section are closed. Danger: Never work on a powered ACS 1000. The main circuit breaker and the input isolators must always be opened and locked in “OPEN” position. Do not access the main power circuit nor the motor as long as the system is not grounded. When switching off the mains, always allow the intermediate circuit capacitors to discharge before grounding and starting work on the frequency converter, the motor or the motor cable. The ACS 1000 and adjoining equipment must be properly grounded and the auxiliary supply voltage must be switched off prior to starting with any work. Danger: Some loads may apply a mechanical torque on the motor shaft! If the motor can rotate due to such a load, always disconnect, short-circuit or mechanically block the motor before you start work. Danger: There can be dangerous voltages inside the ACS 1000 from external control circuits (measurement inputs from PT’s etc.) even if the ACS 1000 mains power and auxiliary power are shut off. Take appropriate measures when working with the unit, i.e deenergize and disconnect all such external devices (auxiliary supply, heaters, coolers, I/O-interfaces) before you start work. Danger: The grounding isolator may become ineffective if the power circuit is opened. The main circuit breaker and the input isolators must always be opened and locked in “OPEN” position. Any external ground switch must be closed and locked. Prior to start working on the ACS 1000 the general safety regulations in Chapter 1 - Safety Instructions must be read and understood. ABB Industrie AG declines all liability for any possible damage resulting from failure or negligence to observe these warnings. Alarm and Fault Handling If a disturbance occurs anywhere in the converter or in related equipment, it will be indicated with an error message on the CDP 312 control panel or, as alternative, on the DriveWindow error display. Two error message levels are used with the ACS 1000: • Fault: a fault is initiated by a serious disturbance in the converter or in related equipment (transformer, motor etc.) and always implies a converter trip. The converter will remain in tripped state (with the exception of a few faults where the converter will resume operation automatically after the disturbance has disappeared). 8-2 (of 38) 3BHS102769 ACS 1000 User’s Manual, Rev. C