Download Introduction - IMB Vadkert Kft.
Transcript
Chapter 6 inverter of function parameter No. 147 Code P09.08 Describing LED/OLED Keyboard display Setting range Deceleration time of JOG operation 0.1~3600.0s Factory setting Type setting Change ◇ Define the presetting frequency and acceleration and deceleration time for the JOG operation. The start and stop method of JOG operation is: direct start and halt with deceleration. Acceleration time of JOG refers to the time required by AC frequency vector inverter from 0Hz to maximum output power (P01.07) Deceleration time of JOG refers to the time required by AC frequency vector inverter from maximum output power to 0Hz (P01.07) 148 P09.09 Hopping frequency 0.00~P01.07(maximum frequency) 0.00Hz ◇ 149 P09.10 Range of hopping frequency 0.00~P01.07(maximum frequency) 0.00Hz ◇ When the frequency set is within the scope of hopping frequency, actual operation frequency will be the boundary of hopping frequency.. The setting of hopping frequency can make AC frequency vector inverter avoid mechanical resonance point of load. And this AC frequency vector inverter can set one hopping frequency point. If set all hopping frequency points to zero, then this function wouldn’t take effect. Just as chart 5-14. Chapter 6 150 P09.11 Range of pendulous frequency 0.0~100.0%( relative setting frequency) 0.0% ◇ 151 P09.12 Range of jumping frequency 0.0~50.0%(relative range of pendulous frequency) 0.0% ◇ 152 P09.13 Rise time pendulous frequency 0.1~3600.0s 5.0s ◇ 153 P09.14 Fall time pendulous frequency 0.1~3600.0s 5.0s ◇ 102