P1.07
CI min. given
Range: 0.00~ P1.09
0.00V
Corresponding freq to CI Range: 0.00~upper limit
P1.08
0.00Hz
min. given
freq
P1.09 CImax. Given
Range: P1.07 ~10.00V
10.00V
Corresponding freq to CI Range: 0.00~upper limit
P1.10
50.00Hz
max. given
freq
P1.11
Max. input PLUSE freq
Range: 0.1~20.0K
10.0K
P1.12 PLUSE min given
Range: 0.0~P1.14
0.0K
Corresponding freq to
Range: 0.00~upper limit
P1.13
0.00Hz
pulse min. given
freq
P1.14 Pulse max. given
Range: P1.12~P1.11
10.0K
Corresponding freq to
Range: 0.00~upper limit
P1.15
50.00Hz
pulse max. given
freq
When selects VI, CI or pulse frequency input as open loop frequency setting channel,
the relationship between frequency given and setting frequency as follow:
Channel
Channel
Channel gains
Frequency
selection
filtering
P1.01/P1.06
curve
Frequency
P0.01
P1.00
setting
setting
The relationship between VI and setting frequency as follow.
Setting freq
Setting freq
Fmax
Fmax
Fmin
Fmin
A
A
Amin
Amin
Amax
(1) Positive effect
A: VI given
Amin: Min
Amax: Max
Amax
(2) Negative effect
Pmin: corresponding Freq to Min given
Pmax: corresponding Freq to Max given