Download CC-Link IE Field Network Digital-Analog
Transcript
CHAPTER 8 FUNCTION 8.5 Range Switching Function The output range can be selected for each channel from the following ranges: • Factory default range (4 to 20mA, 0 to 20mA, 1 to 5V, 0 to 5V, -10 to 10V) • User range (user range setting 1, user range setting 2) (1) Setting procedure 1. Set "Parameter write" for "Method selection". "CC IE Field Configuration" window [CC IE Field Configuration] [Online] Select a D/A converter module in "List of stations". [Parameter Processing of Slave Station] 2. Set "CH D/A conversion enable/disable setting" to "0: Enable". 3. Set "CH Range setting". 8 81 8.5 Range Switching Function When switching the output range, set Disable (OFF) to CH Output enable/disable flag (RY10 to RY13) before setting a value (within the range an external device allows) for CH Digital value (RWw2 to RWw5). For example, when the output range is from 0 to 5V and 12000 is set for CH Digital value (RWw2 to RWw5), 5V is output. In this case, if the output range is changed to -10 to 10V, 7.5V is output because 12000 remains set for CH Digital value (RWw2 to RWw5).