Download 189 Considerations on Numerical Protections for Induction Motors
Transcript
Y0La Z 0s ZT Substation 110 kV Z 0L6 Z BPN 3R Y0L6 2 Z 0L6m I0 Y0L6 2 U0 3ZBS Z 0s - system impedance R - high value resistance 346 Z 0L6 , Y0L6 - cable 6 kV, 185 mmp, 1.85 km Z 0T - transformer 110/22 kV, 25 MVA Y0La - other cables 6 kV, 185 mmp, 10 km Z BPN - nul coil Z BS - arc suppression coil Z 0L6m - cable 6 kV, 70 mmp, 300 m Figure 3. Zero sequence diagram for an fault at the motor terminals, 200 kW, 6 kV Sequence impedances to the fault K2: Y Y Y Z 2 Z ds Z T || L 6 La Z L 6 || L 6 2 2 2 (2) Y 0 L6 Y 0 L 6 Y 0 La Z 02 Z BPN 3 Z BS || R || Z 0 L 6 || 2 2 2 Table 1 presents the fault current given by the supply network of the motor, for the defects to its terminals. Table 1. Calculation of fault currents in the supply network of the motor 6 kV No. Parameter Calculation UM Value Observarelation tions 1. Minimum threeA 7581.96 c=1.0 c U n phase short circuit I k 31min 3 Z 1 current, K1 2. Maximum threephase short circuit current, K1 I k 31max c U n 3 Z 1 192 A 8340.16 c=1.1