TROUBLESHOOTING - REPAIRS 8.5.1.2 - Description of inspection duties - Liquid chiller with scroll compressor(s) START UP - Check unit installation - Check water flow and water circuit ancillaries - Check safety devices - Check leaktightness - Configuration of the microprocessor based management system (if used) - Verification of operating parameters and unit performance - Transmission of the machine service log 500 H / 1000 H VISITS - Post wear in inspection - Oil acidity test, leak test - Replacement of the filter-drier cartrides depending on the results of the test above. - Monitor unit performance and any eventual variations linked to use of the installation. INSPECTION VISIT - Leak test - Operating test with record of measurements taken and functional analysis. MAJOR TECHNICAL INSPECTION - Inspection visit - Acid test - Oil change if necessary - Replacement of filter-drier cartridges - Check up on the microprocessor based management system (if used) - Adjustment of safety devices - Verification of unit interlocks - Lubrication of bearings / dampers if necessary TUBE ANALYSIS - Inspection of water cooled evaporator and condenser tube bundles with an eddy current test to enable potentially serious problems to be anticipated. - Frequency : Every 5 years up to 10 years (depending on the quality of water), then every 3 years. Installation - Operation - Maintenance manual (IOM) • ECOLOGIC RANGE - 0605-E • 35 •