32 Parameter Register Interface Bit 21 22 23-31 Warning -15V Supply Out of Tolerance Vin Low Voltage Reserved 4.2.2.12 Fault Status Fault bits are active when set to a ‘1’ and not present when set to a ‘0’. If a fault occurs, the corresponding bit is set to a ‘1’ and remains set until a “1” is written to the Fault Reset command register (PID 0x0004). When a fault occurs, the controller will go to the FAULT state and the converter will stop operating. The controller will stay in the FAULT state until the Fault Reset command is received. See section 2.4 for details on each fault condition. The fault bits are mapped as follows: Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29-31 Fault IPM Hardware Over Temperature IPM IGBT Error IPM S/W Over Temperature S/W Phase A Over Current S/W Phase B Over Current S/W Phase C Over Current Reserved Reserved Reserved Reserved Reserved Reserved Output Over Current Reserved S/W Vin Over Voltage Reserved Reserved S/W Output Over Voltage Reserved Reserved Auxiliary Over Temperature Calibration Error Pre-Charge Timeout Pre-Charge Contactor Fault Input Contactor Fault Relay Driver Communications Timeout Configuration Memory S/W Vin Under Voltage Reserved for future use Interleaved Buck/Boost DC/DC Controller User’s Manual