Download Rexroth Frequency Converter
Transcript
VFC x610 Series Bosch Rexroth AG Diagnosis 13.3.3 Error 3 (OC-3): Overcurrent during Deceleration Possible reason Solution Excessively short deceleration time Excessive load rotation inertia Motor power and frequency converter power do not match Excessive overexcitation braking factor Wrong motor parameter setting Increase deceleration time (E0.27) Use suitable brake components Motor power has to match with frequency converter power Reduce [E0.55] Correct motor parameters setting 13.3.4 Error 4 (OE-1): Overvoltage at Constant Speed Possible reason Solution Surge voltage from power supply Motor to earth short circuit causes DC-bus capacitors overcharged Excessive load rotation inertia Noise interference Check input power supply Check motor connection Use suitable brake components Check wiring of control circuit, main circuit and grounding 13.3.5 Error 5 (OE-2): Overvoltage during Acceleration Possible reason Solution Surge voltage from power supply Check input power supply Motor to earth short circuit causes Check motor connection DC-bus capacitors overcharged Direct start during motor running Restart after motor stop or start with speed capture (E0.35) Increase acceleration time (E0.26) or use S-curve (E0.25, Excessively short acceleration time E0.28, E0.29) DOK-RCON04-VFC-x610***-IT01-EN-P 171/259