Download E650 Series 3
Transcript
Device description 23/96 +A +THDA = +A - (+A fundamental) +THDA -A -THD A = -A - (-A fundamental ) -THDA Figure 17 Calculation of total harmonic distortion In addition, the following absolute and relative THD values available: THD of active energy (relative to the nominal active energy) Losses THD of phase voltages (absolute) THD of voltage (relative to the nominal voltage) THD of phase currents (absolute) THD of phase current (relative to the nominal current) Depending on the metering point in the network, the meter does not only measure the net energy that is transferred from the power station to the user but also the line losses (caused by the copper resistance RCu) and the transformer losses (caused by the iron resistance RFe). Metering point A Metering point B RFe RCu Generator Metering point C Load Transmission Production Meter A Meter B Customer Figure 18 Calculation of Losses Line losses are caused by the copper resistance RCu of the transmitting line. The copper resistance is only effective if there is a load and therefore current is actually flowing. On Load Active OLA for line losses of active energy The transformer losses represent all losses of the transformer. They are mainly caused by the iron core of the transformer. Transformer losses (equivalent resistance RFe) are present whenever the transformer is connected to the network. No Load Active NLA for transformer losses of active energy Based on the IRMS and URMS values, the microprocessor generates the following measured quantities: OLA On load active. Line (copper) losses of active energy. OLA = I2h x RCu. The value of RCu can be set by parameterisation. NLA No load active. Transformer (iron) losses of active energy. NLA = U2h / RFe. The value of RFe can be set by parameterisation. I2h (Cu) Ampere square hours (with RCu = 1) 2 U h (Fe) Voltage square hours (with RFe 1 M) D000030110 en g – E650 Series 3 – ZMD400AT/CT, ZFD400AT/CT – User Manual © Landis+Gyr