Diagnostics
Trouble Shooting via PROFIBUS DP Diagnostic Messages
Trouble
Shooting
General
Information
In addition to the evaluation of the diagnostic message, there are the following
important error possibilities:
l Comparison of the configured module type
l Examination of the voltage supplies to the modules
l Comparison of the configured addresses with the specified addresses on the bus
adapter
l Examination of the parameterization in the case of complex (analog) modules
l Taking into consideration EMC measures and potential equalization
l Examining cabling (bus connector screws, correct cable assignment, terminal
resistors, appropriate connectors etc.)
l General contact problems with connections
Overview of
diagnostic
Examples
The diagnostic data of a 170 AMM 090 00 in the following cases can be found in the
table:
70
Case No.
Meaning
1
Output state
The I/O base is supplied with voltage, the Profibus is correctly
configured and running. The "BF" LED on the communications adapter
of the AMM 090 is off. The I/O base has not, however, been
parametrized.
2
Error in parameterization.
The I/O base was mistakenly parameterized as 170 AAO 921 during
the bus configuration. The PROFIBUS is running but the "BF" LED on
the communications adapter of the AMM is lit.
3
Slave is not reporting (master diagnostics):
One slave was properly configured. However, it cannot be found
because the bus connector was disconnected or the voltage supply
was interrupted.
4
Valid parameters:
One set of valid parameters has been transferred to the AMM 090
5
Invalid parameters:
One set of invalid parameters has been transferred to the AMM 090