Download PLC Software MANUAL - Xinje-support-centre
Transcript
Specify the set value Write the indirect data register the contents of the data memory indirect pre-written 《Constant (K)》 X0 program or through the switch T10 input values. K100 In keeping with the register specified as a power outage, 《Register (D)》 X0 please pay attention to the MOV K200 battery voltage, if less than the D5 value set will result in an X1 T10 unstable situation. D5 T10 is the timer with 100ms as the unit. Specify 100 as the constant, then 0.1s*100=10s timer works; Timer Value Timer T0~T599 is 16 bits linear increment mode (0~K32,767), when the timer’s value reaches the max value K32767, it stops timing. The timer’s status keeps still; (Output Delay off timer) Action Example X0 T2 Y0 Y0 X0 T2 X0 K200 T2 Y0 X000 is ON, the output Y000; When the X000 by the ON → OFF, it will delay T2 (20 seconds) time, the output Y000 was disconnected. (Flicker) X0 Counter T1 T2 T1 K20 X0 T2 K10 T1 T2 T1 Y0 Y0 PLC Software Manual Page 39 of 365 LMAN021_R2V2
Related documents
1 Program Summary
1 Program Summary
Onkyo SKC-230C User's Manual
Vivotek FD8363 User`s manual
Cal Flame B-270 Specifications
XCM motion controller
XP3-16series integrated PLC&HMI User manual
XINJE XP/XMP
Casio MA1007-A User`s manual
Rockhood Automation XC Series PLC
XP/XMP-18 series - Spectra Technologies
C++: A Beginner`s Guide, Second Edition